High Voltage Testing of a 5-meter Prototype Triaxial HTS Cable
Conference
·
OSTI ID:931954
- ORNL
High voltage tests were performed on a 5-m long prototype triaxial HTS cable (supplied by Ultera) at ORNL in preparation for installation of a 200-m HTS cable of the same design at the AEP utility substation in Columbus, Ohio. The triaxial design comprises three concentric phases and shield around a common former with the phase to phase dielectric at cryogenic temperature. Advantages of this design include increased current density, a reduced amount of HTS tape needed, and reduced heat load. The phase to phase voltage will be 13.2 kVrms (7.6 kVrms to ground). Preliminary testing was done on half-scale and full-scale terminations which successfully passed AC withstand, partial discharge, and impulse tests. High voltage tests conducted on the 5-m cable with the cable straight and after bending 90 degrees were ac withstand to 39 kVrms, partial discharge inception, and a minimum of 10 positive and 10 negative lightning waveform impulses at 110 kV. Phase to phase insulation was tested by applying high voltage to each phase one at a time with all the other phases grounded. Partial discharge data will be presented. The 5-m prototype triaxial HTS cable passed all the HV tests performed, with a PD inception voltage significantly above the required voltage.
- Research Organization:
- Oak Ridge National Laboratory (ORNL)
- Sponsoring Organization:
- OE USDOE - Office of Electric Transmission and Distribution
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 931954
- Country of Publication:
- United States
- Language:
- English
Similar Records
Triaxial HTS Cable for the AEP Bixby Project
Qualification High Voltage Testing of Short Triax HTS Cables in the Laboratory
Development and practical operation of perfluorocarbon immersed 275kV transformers with compressed SF6 gas insulation
Conference
·
Sun Dec 31 23:00:00 EST 2006
·
OSTI ID:931667
Qualification High Voltage Testing of Short Triax HTS Cables in the Laboratory
Journal Article
·
Wed Dec 31 23:00:00 EST 2008
· IEEE Transactions on Applied Superconductivity
·
OSTI ID:963715
Development and practical operation of perfluorocarbon immersed 275kV transformers with compressed SF6 gas insulation
Journal Article
·
Fri Mar 31 23:00:00 EST 1995
· IEEE Transactions on Power Delivery
·
OSTI ID:64428