Development and practical operation of perfluorocarbon immersed 275kV transformers with compressed SF6 gas insulation

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.400842· OSTI ID:64428
; ; ; ;  [1];  [2]; ; ;  [3]
  1. Hitachi Ltd. (Japan)
  2. Kyushu Kyoritu Univ., Kitakyushu (Japan)
  3. Chubu Electric Power Co., Inc., Nagoya (Japan)
A perfluorocarbon (PFC) immersed 275kV transformer with compressed SF6 gas insulation has been under development. This paper clarified the AC partial discharge inception voltage and time characteristics of PFC immersed insulation and also clarified that a prototype 275kV 100MVA three phase transformer could be worked without any trouble during the long-term over voltage test. This prototype proved that it had the AC partial discharge inception strength of higher than 1.5 times of the AC test voltage and the lightning impulse breakdown strength of 1.5 times of the test voltage. A 275kV 250MVA three phase transformer was developed and practically operated at the outdoor substation of Chubu Electric Power Co., Inc. This transformer has been successfully operated until now and the detailed internal inspection of the transformer was carried out after one year and 9 months of the successful practical operation and no significant abnormal condition was recognized.
OSTI ID:
64428
Report Number(s):
CONF-940702--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 2 Vol. 10; ISSN ITPDE5; ISSN 0885-8977
Country of Publication:
United States
Language:
English

Similar Records

Development of a perfluorocarbon liquid immersed prototype large power transformer with compressed SF sub 6 insulation
Journal Article · Mon Jul 01 00:00:00 EDT 1991 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5841665

Development of 275kV gas cooled type gas-insulated power transformer
Journal Article · Thu Dec 31 23:00:00 EST 1992 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6411199

Diagnostic techniques and apparatus for detecting faults in perfluorocarbon liquid immersed transformers
Journal Article · Sun Mar 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:244828