Natural contamination test of insulators with dc voltage energization at inland areas

Journal Article · · IEEE Trans. Power Del.; (United States)
DOI:https://doi.org/10.1109/61.193992· OSTI ID:6494898
; ;  [1]
  1. Central Research Institute of Electric Power Industry, Tokyo (JP)
This report describes the natural contamination test results of insulator strings at inland areas. Natural exposure tests with -280 kV dc voltage energization were carried out for 5 years. The effect of dc voltage application on salt deposit was not notable except on the both sides of the insulator strings. These results are the same as those obtained in sea-side testing stations. The maximum value of leakage current was 3 mA and no flash-over occurred with electrical stress per unit string length of about 100 kV/m. The application of these results to insulation design for HVDC transmission lines is also discussed.
OSTI ID:
6494898
Journal Information:
IEEE Trans. Power Del.; (United States), Journal Name: IEEE Trans. Power Del.; (United States) Vol. 3:4; ISSN ITPDE
Country of Publication:
United States
Language:
English

Similar Records

Round-robin artificial contamination test on high voltage dc insulators
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Transactions on Power Delivery · OSTI ID:136579

BPA's extra high voltage dc tests, contaminated insulators
Journal Article · Sun Oct 01 00:00:00 EDT 1967 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5961380

Measurements of voltage distribution on suspension insulators for HVDC transmission lines
Journal Article · Mon Aug 01 00:00:00 EDT 1983 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5389003