Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

BPA's extra high voltage dc tests, contaminated insulators

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)
Laboratory tests were conducted to determine the dc flashover characteristics of clean, artificially and naturally contaminated transmission line suspension insulators. Direct current flashover of clean and contaminated insulators in the fog chamber is a linear function of string length up to 350 kV. Comparative data are presented on a number of specimens for clean, wet, and contaminated insulators in the fog chamber. BPA's fog chamber tests on artificially contaminated insulators are equivalent to severe natural contamination.
OSTI ID:
5961380
Journal Information:
IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. 86:10; ISSN IEPSA
Country of Publication:
United States
Language:
English

Similar Records

Round-robin artificial contamination test on high voltage dc insulators
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Transactions on Power Delivery · OSTI ID:136579

BPA's extra high voltage dc tests, outdoor flashover
Journal Article · Sun Oct 01 00:00:00 EDT 1967 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5855633

Natural contamination test of insulators with dc voltage energization at inland areas
Journal Article · Sat Oct 01 00:00:00 EDT 1988 · IEEE Trans. Power Del.; (United States) · OSTI ID:6494898