Harmonic analysis of induction watthour meter performance
Journal Article
·
· IEEE Trans. Power Appar. Syst.; (United States)
A mathematical nonlinear model is developed to simulate the performance of an induction watthour meter for nonsinusoidal voltage and current waves. The computation results show that for the special case where the voltage is purely sinusoidal, the measurement error caused by the nonlinear magnetic circuits is generally small unless the current wave contains a relatively large third harmonic component. However, when the voltage and current waves are both nonsinusoidal, the registration error can be relatively large even for a small voltage distortion. This is attributed not only to the nonlinearity but also to the drooping frequency response curve of the meter. In both cases, the sign of the registration error depends largely on the phase angles of voltage and current harmonics with respect to their fundamentals. A comparison shows that the computation results are consistent with the experimental ones which are available in the literature.
- Research Organization:
- Electrical and Computer Engineering Department, Louisiana State University, Baton Rouge, LA
- OSTI ID:
- 6253634
- Journal Information:
- IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. PAS-104:2; ISSN IEPSA
- Country of Publication:
- United States
- Language:
- English
Similar Records
Watthour meter accuracy under controlled unbalanced harmonic voltage and current conditions
Induction varhour and solid-state varhour meters performances on nonlinear loads
On the accuracy of watt-hour meters in nonsinusoidal environment
Journal Article
·
Sun Dec 31 23:00:00 EST 1995
· IEEE Transactions on Power Delivery
·
OSTI ID:218286
Induction varhour and solid-state varhour meters performances on nonlinear loads
Journal Article
·
Mon Oct 01 00:00:00 EDT 1990
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
·
OSTI ID:6208346
On the accuracy of watt-hour meters in nonsinusoidal environment
Conference
·
Sat Dec 30 23:00:00 EST 1995
·
OSTI ID:427917
Related Subjects
200300* -- Electric Power Engineering-- Power Transmission & Distribution-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
ACCURACY
ELECTRIC MEASURING INSTRUMENTS
ELECTRIC POTENTIAL
ELECTRICAL EQUIPMENT
EQUIPMENT
FREQUENCY RESPONSE TESTING
HARMONICS
INDUCTION
MATHEMATICAL MODELS
MEASURING INSTRUMENTS
METERING
METERS
OSCILLATIONS
PERFORMANCE
POWER DISTRIBUTION SYSTEMS
POWER METERS
POWER TRANSMISSION LINES
SIMULATION
TESTING
24 POWER TRANSMISSION AND DISTRIBUTION
ACCURACY
ELECTRIC MEASURING INSTRUMENTS
ELECTRIC POTENTIAL
ELECTRICAL EQUIPMENT
EQUIPMENT
FREQUENCY RESPONSE TESTING
HARMONICS
INDUCTION
MATHEMATICAL MODELS
MEASURING INSTRUMENTS
METERING
METERS
OSCILLATIONS
PERFORMANCE
POWER DISTRIBUTION SYSTEMS
POWER METERS
POWER TRANSMISSION LINES
SIMULATION
TESTING