Induction varhour and solid-state varhour meters performances on nonlinear loads
Journal Article
·
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
- Dept. of Electrical Engineering, Louisiana Techology Univ., Ruston, LA (US)
Experimental measurements of solid-state and induction varhour meters operating in the presence of steady-state nonsinusoidal currents are presented. A computer-based data acquisition and analysis system is used to determine the various electrical quantities of some common nonlinear three-phase loads. The basic operating principles of the varhour meters are reviewed along with the nature of reactive power and energy for nonsinusoidal waveforms. Test results confirm that for nonlinear loads driven by sinusoidal voltages, both types of varhour meters register the fundamental displacement voltampere hours only and do not respond to distortion voltampere hours.
- OSTI ID:
- 6208346
- Journal Information:
- IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) Vol. 5:4; ISSN 0885-8977; ISSN ITPDE
- Country of Publication:
- United States
- Language:
- English
Similar Records
Harmonic analysis of induction watthour meter performance
Performance of electric power meters and analyzers in adjustable-speed drive applications
A survey of North American electric utility concerns regarding nonsinusoidal waveforms
Journal Article
·
Thu Jan 31 23:00:00 EST 1985
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:6253634
Performance of electric power meters and analyzers in adjustable-speed drive applications
Conference
·
Tue Dec 30 23:00:00 EST 1997
·
OSTI ID:345229
A survey of North American electric utility concerns regarding nonsinusoidal waveforms
Journal Article
·
Sun Dec 31 23:00:00 EST 1995
· IEEE Transactions on Power Delivery
·
OSTI ID:218287