Energy-efficient management of lighting in a Veterans Administration medical center
More thn 200 solid-state fluorescent ballasts were installed in representative areas of the Veterans Administration Medical Center in Long Beach, California, to determine the cost-effectiveness of the installation and to measure levels of conducted and radiated electromagnetic interference (EMI). The power, illumination, and EMI levels were measured first as the test sites initially existed, then after the fixtures were cleaned and relamped with energy-saving fluorescent lamps, and finally after the core-coil ballasts were replaced with solid-state ballasts. The annual energy savings for the complete retrofit was measured as 34%. In the director's suite natural daylight was used to supplement the electrical illumination, saving an additional 20 to 25% in energy. Thus, in that area, the total annual energy savings amounted to 51%. EMI levels were measured in general areas (lobby and director's suite), in diagnostic examination areas, and in a coronary care ward. The EMI levels, compared to existing levels, were not considered excessive. All of the above data are analyzed on the basis of life-cycle costing. The analysis is presented on sets of curves relating the cost-effective price of a ballast to the cost of electrical energy.
- Research Organization:
- Lawrence Berkeley Lab., CA (USA)
- DOE Contract Number:
- W-7405-ENG-48
- OSTI ID:
- 6163883
- Report Number(s):
- LBL-12659; ON: DE81029433
- Country of Publication:
- United States
- Language:
- English
Similar Records
Energy savings with solid-state ballasts in a Veterans Administration medical center
Energy savings with solid-state ballasts in a V. A. hospital
Electromagnetic interference (EMI) measuremenets of fluorescent lamps operated with solid-state ballasts
Journal Article
·
Sun Oct 31 23:00:00 EST 1982
· IEEE Trans. Ind. Appl.; (United States)
·
OSTI ID:5997681
Energy savings with solid-state ballasts in a V. A. hospital
Conference
·
Fri May 01 00:00:00 EDT 1981
·
OSTI ID:6347711
Electromagnetic interference (EMI) measuremenets of fluorescent lamps operated with solid-state ballasts
Conference
·
Fri May 01 00:00:00 EDT 1981
·
OSTI ID:6201200
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320103* -- Energy Conservation
Consumption
& Utilization-- School
Municipal
& Other Public Buildings-- (-1987)
BALLASTS
CLEANING
COST
DAYLIGHTING
EFFICIENCY
ELECTROMAGNETIC RADIATION
ENERGY EFFICIENCY
ENERGY SYSTEMS
FLUORESCENT LAMPS
INSTALLATION
LIFE-CYCLE COST
LIGHT BULBS
LIGHTING SYSTEMS
MANAGEMENT
MEDICAL CENTERS
RADIATIONS
RETROFITTING
320103* -- Energy Conservation
Consumption
& Utilization-- School
Municipal
& Other Public Buildings-- (-1987)
BALLASTS
CLEANING
COST
DAYLIGHTING
EFFICIENCY
ELECTROMAGNETIC RADIATION
ENERGY EFFICIENCY
ENERGY SYSTEMS
FLUORESCENT LAMPS
INSTALLATION
LIFE-CYCLE COST
LIGHT BULBS
LIGHTING SYSTEMS
MANAGEMENT
MEDICAL CENTERS
RADIATIONS
RETROFITTING