Energy savings with solid-state ballasts in a Veterans Administration medical center
Journal Article
·
· IEEE Trans. Ind. Appl.; (United States)
More than 200 solid-state fluorescent ballasts were installed in representative areas of a federal medical center in Long Beach, CA, to determine the cost effectiveness of such an installation. The power and illumination levels in the test sites were measured first as they initially existed, then after the fixtures were cleaned and relamped with energy-saving fluorescent lamps, and finally after the core-coil ballasts were replaced with solid-state ballasts. The annual energy savings for the completed retrofit was measured as 33.9 percent. In the director's suite natural daylight was used to supplement the electrical illumination, providing an additional 20-25 percent energy savings. Thus in that area the total annual energy savings amounted to 48 percent. All of the measured data are analyzed on the basis of life-cycle costing. The analyses are presented on sets of curves relating the cost-effective price of a ballast to the cost of electrical energy.
- Research Organization:
- Lawrence Berkeley Laboratory, University of California, Berkeley, CA 94720
- OSTI ID:
- 5997681
- Journal Information:
- IEEE Trans. Ind. Appl.; (United States), Journal Name: IEEE Trans. Ind. Appl.; (United States) Vol. 18:6; ISSN ITIAC
- Country of Publication:
- United States
- Language:
- English
Similar Records
Energy savings with solid-state ballasts in a V. A. hospital
Energy-efficient management of lighting in a Veterans Administration medical center
Real energy savings with electronic ballasts
Conference
·
Fri May 01 00:00:00 EDT 1981
·
OSTI ID:6347711
Energy-efficient management of lighting in a Veterans Administration medical center
Technical Report
·
Sat Feb 28 23:00:00 EST 1981
·
OSTI ID:6163883
Real energy savings with electronic ballasts
Technical Report
·
Fri Feb 29 23:00:00 EST 1980
·
OSTI ID:5865319
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320103* -- Energy Conservation
Consumption
& Utilization-- School
Municipal
& Other Public Buildings-- (-1987)
BALLASTS
CALIFORNIA
COST BENEFIT ANALYSIS
ENERGY
FEDERAL REGION IX
FLUORESCENT LAMPS
INSTALLATION
LIGHT BULBS
MEDICAL CENTERS
NATIONAL ORGANIZATIONS
NORTH AMERICA
RETROFITTING
TESTING
US ORGANIZATIONS
USA
320103* -- Energy Conservation
Consumption
& Utilization-- School
Municipal
& Other Public Buildings-- (-1987)
BALLASTS
CALIFORNIA
COST BENEFIT ANALYSIS
ENERGY
FEDERAL REGION IX
FLUORESCENT LAMPS
INSTALLATION
LIGHT BULBS
MEDICAL CENTERS
NATIONAL ORGANIZATIONS
NORTH AMERICA
RETROFITTING
TESTING
US ORGANIZATIONS
USA