Electromagnetic interference (EMI) measuremenets of fluorescent lamps operated with solid-state ballasts

Conference ·
OSTI ID:6201200
Solid-state ballasts were placed in fluorescent lamps in various areas of a hospital to determine if these high-frequency systems would adversely affect any hospital operations. The general areas tested included a lobby and an office space. Potentially sensitive areas containing hospital diagnostic and monitoring equipment, including a computerized axial tomography (CAT) scanning room, an electroencephalograph (EEG) examination room, and a coronary ward were also tested. The measurement techniques are described and the results discussed with respect to the existing RFI environment and with respect to EMI radiated and conducted limits specified by the Federal Communications Commission and the Federal Drug Administration.