Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

The effects of steep-front, short-duration impulses on power distribution components

Conference ·
DOI:https://doi.org/10.1109/61.53073· OSTI ID:6069905

A line type pulser has been developed to test the effects of steep-front, short duration (SFSD) pulses on distribution components. Risetime is 50-100 ns, and pulse duration is on the order of 300 ns. Terminators often shattered or punctured rather than flashing over. Insulator flashover voltage is approximately 1.5 times CFO for standard lightning impulses. Arresters exhibit an inductive character, with SFSD peak voltage at 10 kA approximately 4--5 times the 8 /times/ 20 microsecond 10 kA discharge voltage. Polyethylene insulated cable has a characteristic degradation in which failure voltage decreases with number of SFSD pulses. 7 refs., 12 figs., 2 tabs.

Research Organization:
Oak Ridge National Lab., TN (USA)
DOE Contract Number:
AC05-84OR21400
OSTI ID:
6069905
Report Number(s):
CONF-890781-2; ON: DE89012338
Country of Publication:
United States
Language:
English