Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

The effects of steep-front, short-duration impulses on power distribution components

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
DOI:https://doi.org/10.1109/61.53073· OSTI ID:7080569
; ;  [1];  [2]
  1. Mississippi State Univ., Mississippi State, MS (USA)
  2. Oak Ridge National Lab., TN (USA). Energy Div.

A line type pulser has been developed to test the effects of steep-front, short duration (SFSD) pulses on distribution components. Risetime is 50-100 ns, and pulse duration is on the order of 300 ns. Terminators often shattered or punctured rather than flashing over. Insulator flashover voltage is approximately 1.5 times CFO for standard lightning impulses. Arresters exhibit an inductive character, with SFSD peak voltage at 10 kA approximately 4-5 times the 8 {times} 20 microsecond 10 kA discharge voltage. Polyethylene insulated cable has a characteristic degradation in which failure voltage decreases with number of SFSD pulses.

DOE Contract Number:
AC05-84OR21400
OSTI ID:
7080569
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) Vol. 5:2; ISSN 0885-8977; ISSN ITPDE
Country of Publication:
United States
Language:
English