Transient overvoltages and overcurrents during line fault tests on the Hokkaido-Honshu HVDC line
A series of line fault tests have been conducted at completion of Stage I of the Hokkaido-Honshu HVDC Link of Electric Power Development Co., Ltd., prior to its commercial operation, in order to study transient overvoltages and overcurrents and to confirm safety operation of system protecting devices in case of DC transmission line faults. The Hokkaido-Honshu HVDC Link is a metallic return HVDC overhead line and cable transmission system, currently being a monopolar system. For this, measurements were conducted this time on reverse polarity overvoltages occurring on main line cable, return line overvoltages, fault arc dynamic characteristics, and DC bypass current through the AC system. The results obtained were then compared with the analysis results by the HVDC surge similator or digital simulation conducted for system design prior to the field tests. As a result, a close accordance was found between them, in confirmation of the effectiveness of the analysis method.
- Research Organization:
- Central Research Inst. of Electric Power Industry, Tokyo
- OSTI ID:
- 5957026
- Journal Information:
- IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. PAS-101:8; ISSN IEPSA
- Country of Publication:
- United States
- Language:
- English
Similar Records