Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

New protection method for HVDC lines including cables

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.473346· OSTI ID:152960
For the third project of the Hokkaido-Honshu HVDC Link in Japan, called the HVDC Link III project (rated at 250 kVdc-1,200 A-300 MW), the authors developed an HVDC transmission line protection method based on a new working principle that allows high-speed and highly sensitive detection of faults, enhancing reliability in the supply of electric power. In general, increasing the sensitivity of relays will lead to an increased likelihood of undesired operation whereas lowering the sensitivity will impair the responsiveness of the relays. The proposed method meets these apparently incompatible requirements very well. Basically classified as a differential scheme, the HVDC transmission line protection method compensates for a charging and discharging current that flows through the line-to-ground capacitance at times of voltage variations caused by a line fault or by the operation of dc power systems. The developed protection method is also characterized in that it uses current changes induced by voltage variations to restrain the operation of a relay. This configuration has made the proposed method far superior in responsiveness and sensitivity to the conventional protection method. A simulation using an EMTP (Electro-Magnetic Transients Program) was conducted on this method. Developed relay equipment embodying the new protection method was subjected to various verification tests, where this equipment was connected to a power system simulator, before being delivered to the HVDC Link III facility.
OSTI ID:
152960
Report Number(s):
CONF-950103--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 4 Vol. 10; ISSN ITPDE5; ISSN 0885-8977
Country of Publication:
United States
Language:
English

Similar Records

Transient overvoltages and overcurrents during line fault tests on the Hokkaido-Honshu HVDC line
Journal Article · Sun Aug 01 00:00:00 EDT 1982 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5957026

HVDC submarine cables for the Hokkaido Honshu linkage
Journal Article · Tue Mar 31 23:00:00 EST 1981 · Energy Dev. Jpn.; (United States) · OSTI ID:6746405

Advanced study techniques: tools for HVDC systems design