Transient overvoltages on an hvdc bipolar line during monopolar line faults
Conference
·
· IEEE Trans. Power Appar. Syst.; (United States)
OSTI ID:7011933
- Dept. of Water and Power, Los Angeles
A series of monopolar line-to-ground faults were performed on a bipolar hvdc transmission system and the induced transient voltage on the sound pole recorded and compared with various system modelling techniques. Longitudinal overvoltage profiles are developed and selected parameters varied in an investigation of factors influencing overvoltage magnitude and wave shape. Selected examples of field data are included to support the conclusions concerning fault location, distortion, line termination and prefault voltage.
- OSTI ID:
- 7011933
- Conference Information:
- Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Journal Volume: PAS-96:2
- Country of Publication:
- United States
- Language:
- English
Similar Records
Transient overvoltages and overcurrents during line fault tests on the Hokkaido-Honshu HVDC line
Fault surges on HVDC transmission lines in both bipolar operation and monopolar metallic return operation models and comparison with field test results
Transient overvoltages on a three terminal dc transmission system due to monopolar ground faults
Journal Article
·
Sun Aug 01 00:00:00 EDT 1982
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:5957026
Fault surges on HVDC transmission lines in both bipolar operation and monopolar metallic return operation models and comparison with field test results
Journal Article
·
Thu Jul 01 00:00:00 EDT 1982
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:5224016
Transient overvoltages on a three terminal dc transmission system due to monopolar ground faults
Journal Article
·
Sat Mar 31 23:00:00 EST 1990
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
·
OSTI ID:6731428