A new Fourier method for evaluating generation system reliability indices

Journal Article · · IEEE Trans. Power Syst.; (United States)

A new, robust, and computationally efficient Fourier method for evaluating the loss of load probability and expected value of energy not served in a generation system is presented in this paper. An efficient algorithm is developed for computing the transformed probability density function of outages of all the generating units of the system. The fast Fourier transform algorithm is then used for transforming the load duration curve, and for inverse transformation of the product of the transformed outage function and the transformed load duration curve. As the method does not involve any approximation, it is expected to yield highly accurate results in all situations. Being a Fourier domain method, significant saving in computational effort results for systems with identical units. The application of the method is illustrated for a typical medium-sized system.

Research Organization:
Indian Institute of Technology, New Delhi 110 016
OSTI ID:
5433741
Journal Information:
IEEE Trans. Power Syst.; (United States), Journal Name: IEEE Trans. Power Syst.; (United States) Vol. PWRS-1:3; ISSN ITPSE
Country of Publication:
United States
Language:
English