Application of imitation steam'' systems to hot water district heating and cooling systems
Pequod Associates, Inc. and District Energy St. Paul, Inc. installed a pilot project of an innovative District Heating technology through a contract with the US DOE. This applied research was funded by the Energy Research and Development Act (94--163) for District Heating and Cooling Research. The experimental design is an intervention technique that permits hot water district heating systems to connect to buildings equipped with steam heating systems to connect to buildings equipped with steam heating systems. This method can substantially reduce conversion costs in many older buildings. The method circulates Imitation Steam, which is moist hot air, as a heating medium in standard steam radiators and steam heating coils. Based on the operation of the system during the 1989--90 and 1990--91 winter heating seasons, we conclude the following: the basic concept of using Imitation Steam was proved feasible. The performance of the system can be improved beyond the levels achieved in this installation. Imitation Steam did not cause significant corrosion in the piping system. The technology can be used by other district heating systems to lower conversion costs and increase market penetration. Among the additional benefits from this technology are: eliminating old, inefficient boilers; lower maintenance costs; improved fuel efficiency; reduced emissions.
- Research Organization:
- Pequod Associates, Inc., Boston, MA (United States)
- Sponsoring Organization:
- DOE; USDOE, Washington, DC (United States)
- DOE Contract Number:
- FG01-90CE26601
- OSTI ID:
- 5066089
- Report Number(s):
- DOE/CE/26601-T1; ON: DE92001964
- Country of Publication:
- United States
- Language:
- English
Similar Records
Application of vacuum steam systems to hot water district heating and cooling systems; Phase 2, System design and installation: Final technical report
District heating/cogeneration application studies for the Minneapolis-St. Paul area. Market assessment and economic analysis of the St. Paul district heating system
Building conversion costs and economics for the St. Paul hot-water district-heating market
Technical Report
·
Sun Dec 31 23:00:00 EST 1989
·
OSTI ID:720665
District heating/cogeneration application studies for the Minneapolis-St. Paul area. Market assessment and economic analysis of the St. Paul district heating system
Technical Report
·
Mon Jan 31 23:00:00 EST 1983
·
OSTI ID:6387579
Building conversion costs and economics for the St. Paul hot-water district-heating market
Conference
·
Fri Dec 31 23:00:00 EST 1982
· Proc. Int. Dist. Heat. Assoc.; (United States)
·
OSTI ID:6790052
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320105* -- Energy Conservation
Consumption
& Utilization-- Building Services-- (1987-)
320106 -- Energy Conservation
Consumption
& Utilization-- Building Equipment-- (1987-)
BOILERS
BUILDINGS
COOLING
DISTRICT COOLING
DISTRICT HEATING
DOCUMENT TYPES
EFFICIENCY
ENERGY EFFICIENCY
FEASIBILITY STUDIES
HEAT EXCHANGERS
HEATING
INSTALLATION
PROGRESS REPORT
RETROFITTING
WATER HEATING
320105* -- Energy Conservation
Consumption
& Utilization-- Building Services-- (1987-)
320106 -- Energy Conservation
Consumption
& Utilization-- Building Equipment-- (1987-)
BOILERS
BUILDINGS
COOLING
DISTRICT COOLING
DISTRICT HEATING
DOCUMENT TYPES
EFFICIENCY
ENERGY EFFICIENCY
FEASIBILITY STUDIES
HEAT EXCHANGERS
HEATING
INSTALLATION
PROGRESS REPORT
RETROFITTING
WATER HEATING