REACTOR PLANT CONTAINER INTEGRITY TEST, CORE I, SEED 2. Test Results DLCS- 3570201(T-643733)
Technical Report
·
OSTI ID:4150751
Tests were conducted to prove the integrity of the 48inch butterfly valves in the PWR reactor plant by means of air pressure, visual inspection, and operating check. The leak rate on 1A and 1B exhaust valves was 4.1 psi/hr, while the rate on the 1C and 1D supply valves was 5.6 psi/hr. These leak rates were deemed acceptable by the Atomic Energy Commission. (J.R.D.)