PERIODIC REACTOR PLANT LEAK RATE TEST. CORE 1, SEED 2. Test Results
An investigation was made to determine the magnitude and location of the reactor coolant system leakage of the Shippingport Power Beactor. The "total" plant leakage was indicated by the pressurizer level change since no make-up was added during the test. The "accounted for" leakage was indicated by the flash tank level change and the blowoff tank level change. The relief valves from the pressurizer and reactor were checked for leakage individrually and a combined leakage of 2.84 gal/hr was obtainsd for the 6 valves tested. The system was found to have a total leak rate of 5.65 gal/hr of which 1.17 gal/hr was "accounted for." (M.C.G.)
- Research Organization:
- Duquesne Light Co., Shippingport, Penna.
- NSA Number:
- NSA-15-016689
- OSTI ID:
- 4027929
- Report Number(s):
- DLCS-2110132
- Country of Publication:
- Country unknown/Code not available
- Language:
- English
Similar Records
PERIODIC PRIMARY PLANT LEAK RATE TEST. CORE 1, SEED 2. Test Results T- 641102. First issue, June 14, 1961
PERIODIC REACTOR PLANT LEAK RATE TEST. CORE 1, SEED 2. Test Results T- 641102. First Issue, JUNE 14, 1961
PERIODIC REACTOR PLANT LEAK RATE TEST. CORE I, SEED 2. TEST RESULTS T- 641102
Technical Report
·
Mon Oct 30 23:00:00 EST 1961
·
OSTI ID:4014031
PERIODIC REACTOR PLANT LEAK RATE TEST. CORE 1, SEED 2. Test Results T- 641102. First Issue, JUNE 14, 1961
Technical Report
·
Mon Oct 30 23:00:00 EST 1961
·
OSTI ID:4014030
PERIODIC REACTOR PLANT LEAK RATE TEST. CORE I, SEED 2. TEST RESULTS T- 641102
Technical Report
·
Thu Jan 19 23:00:00 EST 1961
·
OSTI ID:4073757