Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Experimental evaluation of a UHV tower model for lightning surge analysis

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.368374· OSTI ID:40010
; ; ;  [1];  [2];  [3];  [4];  [5]
  1. Tokyo Electric Power Co. (Japan)
  2. Shibaura Inst. of Technology, Tokyo (Japan)
  3. Doshisha Univ., Kyoto (Japan)
  4. Univ. of Tokyo (Japan)
  5. Toyo Univ., Saitama (Japan)

An experimental investigation was performed on UHV tower model for the EMTP multiconductor calculation or lightning overvoltage at substations associated with back-flashover at an adjacent transmission tower. The various lightning surge response characteristics were measured on an actual UHV tower, and parameters of a multistory transmission tower model that can reproduce voltages across the insulator strings, voltages of the crossarms, and voltages of the power lines were determined. A value of 120 {Omega} was determined as the surge Impedance at each section or the multistory tower model, which closely agreed with the tower surge Impedance measured for the UHV tower alone.

OSTI ID:
40010
Report Number(s):
CONF-940110--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 1 Vol. 10; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Multistory transmission tower model for lightning surge analysis
Journal Article · Mon Jul 01 00:00:00 EDT 1991 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5841324

Numerical electromagnetic field analysis of tower surge response
Journal Article · Tue Dec 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:477235

Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning
Journal Article · Sun Mar 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:244838