Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.489361· OSTI ID:244838
; ; ; ; ; ;  [1];  [2];  [3]
  1. Hokuriku Electric Power Co., Toyama (Japan)
  2. CRIEPI, Tokyo (Japan)
  3. Univ. of Tokyo (Japan)

Measurement of lightning surges caused by natural or rocket-triggered lightning strokes has been carried out on a 275 kV test transmission line since 1987. In November 1993, lightning currents at the tower top, the ground wires, the tower legs and the transmission line arresters, along with the voltages across the insulator strings were measured simultaneously four times. One of the four flashes was natural lightning, and its peak value was +132 kA. In this case, the arresters operated, and the insulator voltages where the arresters were equipped were controlled properly. The result of multi-phase analysis by EMTP agreed well with the measured waveforms.

OSTI ID:
244838
Report Number(s):
CONF-950727--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 2 Vol. 11; ISSN ITPDE5; ISSN 0885-8977
Country of Publication:
United States
Language:
English

Similar Records

Multistory transmission tower model for lightning surge analysis
Journal Article · Mon Jul 01 00:00:00 EDT 1991 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5841324

Experimental evaluation of a UHV tower model for lightning surge analysis
Journal Article · Sat Dec 31 23:00:00 EST 1994 · IEEE Transactions on Power Delivery · OSTI ID:40010

Observation and analysis of multiple-phase grounding faults caused by lightning
Journal Article · Sun Dec 31 23:00:00 EST 1995 · IEEE Transactions on Power Delivery · OSTI ID:218319