Early monitoring results of two voltage sag ride-through devices at a plastics extrusion plant
Technical Report
·
OSTI ID:376842
- Electrotek Concepts, Inc., Knoxville, TN (United States)
- Carolina Power & Light Co., Raleigh, NC (United States)
- Electric Power Research Institute, Palo Alto, CA (United States)
Voltage sag mitigation techniques command attention in the power quality arena today due to the increasing numbers of sensitive process loads connected to the utility distribution system. This paper presents monitoring results related to the performance of two such devices applied in different levels of voltage sag coverage. The superconducting storage device is designed to protect sensitive loads without the normal segregation of large-power loads (drives, motors) from low-power/high sensitivity machines (computers, programmable logic controllers). The magnetic synthesizer in this case study protects control circuits and requires separation of these circuits from other loads within the sensitive machine. Both methods are effective in reducing process shutdowns due to voltage sags. Their relative economy depends on the type of disturbances affecting the process and the amount of the customer`s economic losses.
- Research Organization:
- Electric Power Research Inst., Palo Alto, CA (United States); CK and Associates, Albany, CA (United States)
- OSTI ID:
- 376842
- Report Number(s):
- EPRI-TR--104581; CONF-9311343--
- Country of Publication:
- United States
- Language:
- English
Similar Records
Voltage sags in industrial systems
The effects of voltage sags in hospitals
Economics of UPS equipment to ride-through voltage sags
Journal Article
·
· IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6307437
The effects of voltage sags in hospitals
Technical Report
·
Thu Jun 01 00:00:00 EDT 1995
·
OSTI ID:376841
Economics of UPS equipment to ride-through voltage sags
Technical Report
·
Thu Jun 01 00:00:00 EDT 1995
·
OSTI ID:376827