Using Acid Number as a Leading Indicator of Refrigeration and Air Conditioning System Performance
This report summarizes a literature review to assess the acidity characteristics of the older mineral oil and newer polyolester (POE) refrigeration systems as well as to evaluate acid measuring techniques used in other non-aqueous systems which may be applicable for refrigeration systems. Failure in the older chlorofluorocarbon/hydrochlorofluorocarbon (CFC/HCFC) / mineral oil systems was primarily due to thermal degradation of the refrigerant which resulted in the formation of hydrochloric and hydrofluoric acids. These are strong mineral acids, which can, over time, severely corrode the system metals and lead to the formation of copper plating on iron surfaces. The oil lubricants used in the older systems were relatively stable and were not prone to hydrolytic degradation due to the low solubility of water in oil. The refrigerants in the newer hydrofluorocarbon (HFC)/POE systems are much more thermally stable than the older CFC/HCFC refrigerants and mineral acid formation is negligible. However, acidity is produced in the new systems by hydrolytic decomposition of the POE lubricants with water to produce the parent organic acids and alcohols used to prepare the POE. The individual acids can therefore vary but they are generally C5 to C9 carboxylic acids. Organic acids are much weaker and far less corrosive to metals than the mineral acids from the older systems but they can, over long time periods, react with metals to form carboxylic metal salts. The salts tend to accumulate in narrow areas such as capillary tubes, particularly if residual hydrocarbon processing chemicals are present in the system, which can lead to plugging. The rate of acid production from POEs varies on a number of factors including chemical structure, moisture levels, temperature, acid concentration and metals. The hydrolysis rate of reaction can be reduced by using driers to reduce the free water concentration and by using scavenging chemicals which react with the system acids. Total acid number (TAN), which includes both mineral acids and organic acids, is therefore a useful indicator which can be used to monitor the condition of the system in order to perform remedial maintenance, when required, to prevent system failure. The critical TAN value is the acid level at which remedial action should be taken to prevent the onset of rapid acid formation which can result in system failure. The level of 0.05 mg KOH/g of oil was established for CFC/mineral oil systems based on analysis of 700 used lubricants from operating systems and failed units. There is no consensus within the refrigeration industry as to the critical TAN value for HFC/POE systems, however, the value will be higher than the CFC/mineral oil systems critical TAN value because of the much weaker organic acids produced from POE. A similar study of used POE lubricants should be performed to establish a critical TAN limit for POE systems. Titrimetric analysis per ASTM procedures is the most commonly used method to determine TAN values in lubricants in the refrigeration industry and other industries dealing with lubricating oils. For field measurements, acid test kits are often used since they provide rapid, semi-quantitative TAN results.
- Research Organization:
- Air-Conditioning and Refrigeration Technology Institute (US)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EE) (US)
- DOE Contract Number:
- FC05-99OR22674
- OSTI ID:
- 823889
- Report Number(s):
- DOE/OR22764/611-50060-01; ARTI-21CR/611-50060-01; TRN: US200417%%74
- Resource Relation:
- Other Information: PBD: 31 Jul 2003
- Country of Publication:
- United States
- Language:
- English
Similar Records
Study of lubricant circulation in HVAC systems
Solubility, viscosity and density of refrigerant/lubricant mixtures
Related Subjects
AIR CONDITIONING
CARBOXYLIC ACIDS
HYDROFLUORIC ACID
INORGANIC ACIDS
LUBRICATING OILS
ORGANIC ACIDS
PERFORMANCE
PH VALUE
REFRIGERATION
REMEDIAL ACTION
THERMAL DEGRADATION
REFRIGERANT
LUBRICANT
ACIDITY
POLYOLESETER
POE
HFC
HCFC
CFC
TAN
HYDROLYTIC DECOMPOSITION
HYDROLYSIS
TITRIMETRIC ANALYSIS
ION CHROMATOGRAPHY
FREE RADICAL
VOLTAMMETRY
ARTI
21CR