Corrosion Evaluation of Tank 40 Leak Detection Box
'Leak detection from the transfer lines in the tank farm has been a concern for many years because of the need to minimize exposure of personnel and contamination of the environment. The leak detection box (LDB) is one line of defense, which must be maintained to meet this objective. The evaluation of a failed LDB was one item from an action plan aimed at minimizing the degradation of LDBs. The Tank 40 LDB, which failed in service, was dug up and shipped to SRTC for evaluation. During a video inspection while in service, this LDB was found to have black tubercles on the interior, which suggested possible microbial involvement. The failure point, however, was believed to have occurred in the drain line from the transfer line jacket. Visual, metallurgical, and biological analyses were performed on the LDB. The analysis results showed that there was not any adverse microbiological growth or significant localized corrosion. The corrosion of the LDB was caused by exposure to aqueous environments and was typical of carbon steel pipes in soil environments.'
- Research Organization:
- Savannah River Site (SRS), Aiken, SC (United States)
- Sponsoring Organization:
- USDOE
- DOE Contract Number:
- AC09-89SR18035
- OSTI ID:
- 6237909
- Report Number(s):
- WSRC-TR-99-00200; ON: DE00009303
- Country of Publication:
- United States
- Language:
- English
Similar Records
Characterization of Infrequent Samples from The Concentration, Storage, And Transfer Facility: Leak Detection Box (LDB) Drain Cell Sample: February 26, 2023, Sample
Characterization of Infrequent Samples from the Concentration, Storage, and Transfer Facility: Leak Detection Box (LDB) Drain Cell Sample: May 15, 2023, Sample