Title: Design criteria: data acquisition system for waste tank liquid level gauges and SX Tank Farm thermocouples

Technical Report ·
DOI:https://doi.org/10.2172/4400115· OSTI ID:4400115

This design criteria revision (revision 2) will cancel revision 1 and will provide complete functional supervision of the liquid level gauges. A new.counter and an electronic supervisory circuit will be installed in each waste tank liquid level gauge. The electronic supervisory circuit will monitor (via the new counter and a signal from the gauge electronics) cycling of the gauge on a one minute time cycle. This supervisory circuit will fulfill the intent of revision 1 (monitor AC power to the gauge) and, in addition, will supervise all other aspects of the gauge including: the electronics, the drive motor, all sprockets and chain linkages, and the counter. If a gauge failure should occur, this circuit will remove the +12 volts excitation from the data acquisition system inferface board; and the computer will be programmed to recognize this condition as a gauge failure. (auth)

Research Organization:
Atlantic Richfield Hanford Co., Richland, WA (United States)
DOE Contract Number:
AT(45-1)-2130
NSA Number:
NSA-29-010773
OSTI ID:
4400115
Report Number(s):
ARH-2384
Resource Relation:
Other Information: Orig. Receipt Date: 30-JUN-74
Country of Publication:
United States
Language:
English