skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Nitrogen Precooling Heat Exchanger replacement and control system upgrade in Superfluid Cryoplant at CMTF

Conference ·
OSTI ID:1998928

Liquid Nitrogen precooling is used in most Cryoplants to achieve cooldown to 80 K temperature range. In one such system at Fermilab's CMTF Superfluid Cryoplant, where the Helium supply directly exchanges heat with liquid Nitrogen, freezing of Nitrogen occurred inside the heat exchanger due to heat exchanger imbalance during a Cryoplant trip. Trapped vapor pockets of N2 within the frozen heat exchanger channels were formed while warming up the heat exchanger, creating high localized pressure and subsequent damage/rupture of the heat exchanger. Replacement of the heat exchanger was done, and modifications were made in the system to rectify future occurrences. The control system was updated to bypass the heat exchanger entirely if the incoming Helium stream temperature drops below 76 K. This was done by repurposing two control valves as heat exchanger bypass valves that were previously used for a redundant 80 K adsorber in the coldbox. Additional modifications were made to further prevent return of large amount of cold Helium gas from cold end during abrupt Cryoplant shutdown. This modification has ensured high reliability of heat exchanger with prevention of freezing of Nitrogen which can damage the heat exchanger.

Research Organization:
Fermi National Accelerator Laboratory (FNAL), Batavia, IL (United States)
Sponsoring Organization:
USDOE Office of Science (SC), High Energy Physics (HEP)
DOE Contract Number:
AC02-07CH11359
OSTI ID:
1998928
Report Number(s):
FERMILAB-CONF-23-379-TD; arXiv:2308.15615; oai:inspirehep.net:2693873
Country of Publication:
United States
Language:
English

Similar Records

Dynamic Simulation of a Helium Liquefier
Journal Article · Wed Jun 23 00:00:00 EDT 2004 · AIP Conference Proceedings · OSTI ID:1998928

Mathematical modeling of a Fermilab helium liquefier coldbox
Conference · Fri Dec 01 00:00:00 EST 1995 · OSTI ID:1998928

UNIQUE METHOD FOR LIQUID NITROGEN PRECOOLING OF A PLATE FIN HEAT EXCHANGER IN A HELIUM REFRIGERATION CYCLE.
Technical Report · Wed Jun 02 00:00:00 EDT 2004 · OSTI ID:1998928