Title: Enhanced Component Performance Study: Emergency Diesel Generators 1998-2020

Technical Report ·
DOI:https://doi.org/10.2172/1894882· OSTI ID:1894882

This report presents an enhanced performance evaluation of emergency power system (EPS) and high-pressure core spray (HPCS) emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Industry Reporting and Information System (IRIS) data from 1998 through 2020 and (2) maintenance unavailability performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2020. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in NRC probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. The EDG failure modes considered are fail to start (FTS), fail to load and run (FTLR), and fail to run after one hour of operation (FTR>1H). Engineering analyses were performed with respect to time period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed are: subcomponent, failure cause, detection method, recovery, manufacturer, and EDG rating. The following increasing trends were identified for EDGs for the most recent 10-year period: • HPCS EDG FTS failure probability • EPS and HPCS EDG frequency of start demands (demands per reactor year) • EPS and HPCS EDG frequency of FTLR demands. The following decreasing trends were identified for EDGs for the most recent 10-year period: • EPS EDG FTS failure probability • EPS EDG FTLR failure probability • EPS EDG unavailability • EPS and HPCS EDG frequency of FTLR events (failures per reactor year).

Research Organization:
Idaho National Laboratory (INL), Idaho Falls, ID (United States)
Sponsoring Organization:
USDOE Office of Nuclear Energy (NE)
DOE Contract Number:
AC07-05ID14517
OSTI ID:
1894882
Report Number(s):
INL/RPT-22-66601-Rev.0; TRN: US2309083
Country of Publication:
United States
Language:
English

Similar Records

Enhanced Component Performance Study: Emergency Diesel Generators 1998–2022
Technical Report · Sat Jul 01 00:00:00 EDT 2023 · OSTI ID:1894882

Enhanced Component Performance Study: Emergency Diesel Generators 1998–2018
Technical Report · Fri Apr 17 00:00:00 EDT 2020 · OSTI ID:1894882

Enhanced Component Performance Study: Motor-Driven Pumps 1998-2020