Title: Operation and control of hybrid HVDC system with LCC and full-bridge MMC connected in parallel

Journal Article · · IET Generation, Transmission, & Distribution
 [1];  [1];  [2];  [1]
  1. Univ. of Tennessee, Knoxville, TN (United States)
  2. ABB Corporate Research Raleigh, NC (United States)

In this study, a new kind of hybrid high-voltage direct current (HVDC) system is proposed. Each terminal of the proposed system consists of one line commutated converter (LCC) and one full-bridge modular multilevel converter (FB-MMC). The LCC and FB-MMC are connected in parallel so that they can share the same transmission line. The active–reactive power capability of the hybrid HVDC system is extended compared with the conventional LCC-HVDC system, and power reversal control without power interruption can be achieved by the coordination control of LCC and FB-MMC. Besides, the proposed hybrid HVDC system is capable of handling DC fault, because both LCC and FB-MMC have DC fault blocking capability. Moreover, the power rating of FB-MMC can be designed to low value while keeping the bulk-power transmission capability of LCC. A two-terminal bipolar hybrid HVDC system is built in PSCAD/EMTDC. The simulation results verify the effectiveness and feasibility of the proposed hybrid topology and corresponding control strategies.

Research Organization:
Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE
Grant/Contract Number:
AC05-00OR22725
OSTI ID:
1665962
Journal Information:
IET Generation, Transmission, & Distribution, Vol. 14, Issue 7; ISSN 1751-8687
Publisher:
Institution of Engineering and TechnologyCopyright Statement
Country of Publication:
United States
Language:
English

References (32)

Voltage angle lock loop control of the boost type PWM converter for HVDC application journal April 1990
A Review of Hybrid Topologies Combining Line-Commutated and Cascaded Full-Bridge Converters journal October 2017
Control of a hybrid high-voltage DC connection for large doubly fed induction generator-based wind farms journal January 2011
Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC Breakers journal June 2016
A Fast DC Fault Detection Method Using DC Reactor Voltages in HVdc Grids journal October 2018
Enhanced Independent Pole Control of Hybrid MMC-HVdc System journal April 2018
Equivalent Electromagnetic Transient Simulation Model and Fast Recovery Control of Overhead VSC-HVDC Based on SB-MMC journal April 2017
Analysis of Dual-Infeed HVDC With LCC–HVDC and VSC–HVDC journal July 2012
Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC Converter journal October 2014
DC-Side Harmonic Currents Calculation and DC-Loop Resonance Analysis for an LCC–MMC Hybrid HVDC Transmission System journal April 2015
A Series-Connected Topology of a Diode Rectifier and a Voltage-Source Converter for an HVDC Transmission System journal April 2014
HVDC macrogrid modeling for power-flow and transient stability studies in north american continental-level interconnections journal December 2017
Application of GTO voltage source inverter in a hybrid HVDC link journal January 1994
Hybrid high-voltage direct current topology with line commutated converter and modular multilevel converter in series connection suitable for bulk power overhead line transmission journal October 2016
The ABCs of HVDC transmission technologies journal March 2007
Power-Synchronization Control of Grid-Connected Voltage-Source Converters journal May 2010
Master self-tuning VDCOL function for hybrid multi-terminal HVDC connecting renewable resources to a large power system journal September 2017
Investigation of Fault Ride-Through Capability of Hybrid VSC-LCC Multi-Terminal HVDC Transmission Systems journal February 2019
Quasi-dynamic model of VSC-HVDC transmission systems for an operator training simulator application journal October 2018
A LCC and MMC hybrid HVDC topology with DC line fault clearance capability journal November 2014
A novel restart control strategy for the MMC-based HVDC transmission system journal July 2018
Advanced Vector Control for Voltage Source Converters Connected to Weak Grids journal November 2015
Modeling and Control of a Modular Multilevel Converter-Based HVDC System Under Unbalanced Grid Conditions journal December 2012
A Frequency-Based Synchronization Approach for the VSC-HVDC Station Connected to a Weak AC Grid journal June 2017
Complete mathematical model derivation for modular multilevel converter based on successive approximation approach journal December 2015
DC Fault Detection and Location in Meshed Multiterminal HVDC Systems Based on DC Reactor Voltage Change Rate journal June 2017
Self-Start Control With Grouping Sequentially Precharge for the C-MMC-Based HVDC System journal February 2014
Hybrid HVDC for Integrating Wind Farms With Special Consideration on Commutation Failure journal April 2016
Simulation Analysis of Split Connection Mode System Control for XiMeng to TaiZhou UHVDC Project conference November 2018
Fullbridge MMC control for hybrid HVDC systems conference November 2017
Hybrid HVDC converters and their impact on power system dynamic performance conference January 2006
Research on a new scheme of LCC‐HVDC line protection journal January 2017

Similar Records

Control of MMC-HVDC in low-inertia weak grids
Conference · Fri Dec 01 00:00:00 EST 2017 · OSTI ID:1665962

A Station-hybrid HVDC System Structure and Control Strategies for Cross-seam Power Transmission
Journal Article · Mon Jun 15 00:00:00 EDT 2020 · IEEE Transactions on Power Systems · OSTI ID:1665962

A Generalized Precharging Strategy for Soft Startup Process of the Modular Multilevel Converter-Based HVDC Systems
Journal Article · Sun Jan 01 00:00:00 EST 2017 · IEEE Transactions on Industry Applications · OSTI ID:1665962