Title: Qualification for PowerInsight accuracy of power measurements

Technical Report ·
DOI:https://doi.org/10.2172/1121972· OSTI ID:1121972
 [1];  [1];  [1]
  1. Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)

Accuracy of component based power measuring devices forms a necessary basis for research in the area of power-efficient and power-aware computing. The accuracy of these devices must be quantified within a reasonable tolerance. This study focuses on PowerInsight, an out- of-band embedded measuring device which takes readings of power rails on compute nodes within a HPC system in realtime. We quantify how well the device performs in comparison to a digital oscilloscope as well as PowerMon2. We show that the accuracy is within a 6% deviation on measurements under reasonable load.

Research Organization:
Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
USDOE National Nuclear Security Administration (NNSA)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
1121972
Report Number(s):
SAND2013-9639; 482628
Country of Publication:
United States
Language:
English