This study examines the airflow and contaminant transport in an existing room (89 inch x 77 inch x 98 inch) that houses a downdraft table at LLNL. The facility was designed and built in the 1960's and is currently being considered for redesign. One objective of the redesign is to reduce airflow while maintaining or improving user safety. Because this facility has been used for many years to handle radioactive material it is impractical to conduct extensive experimental tests in it. Therefore, we have performed a Computational Fluid Dynamic (CFD) analysis of the facility. The study examines the current operational condition and some other cases with reduced airflow. Reducing airflow will lead to savings in operating costs (lower fan power consumption), and possible improvements in containment from reduced turbulence. In addition, we examine three design (geometry) changes. These are: (1) increasing the area of the HVAC inlet on the ceiling, (2) adding a 15{sup o} angled ceiling inlet and (3) increasing the area of the slot in the doorway. Of these three geometry modifications, only the larger doorway slot leads to improved predicted containment.
Research Organization:
Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
Sponsoring Organization:
Lawrence Livermore National Laboratory (US)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
817257
Report Number(s):
LBNL--53883
Country of Publication:
United States
Language:
English

Similar Records

CFD Investigation of Room Ventilation for Improved Operation of a Downdraft Table: Novel Concepts
Journal Article · Tue Oct 31 19:00:00 EST 2006 · Journal of Occupational and Environmental Hygiene · OSTI ID:1826686

Investigation of room ventilation for improved operation of a downdraft table
Conference · Sat May 01 00:00:00 EDT 2004 · OSTI ID:835163

CFD Investigation of Room Ventilation for Improved Operation of aDowndraft Table: Novel Concepts
Journal Article · Thu Mar 31 23:00:00 EST 2005 · Journal of Occupational and EnvironmentalHygiene · OSTI ID:908163