Effect of outside air ventilation rate on VOC concentrations and emissions in a call center
- LBNL Library
A study of the relationship between outside air ventilation rate and concentrations of VOCs generated indoors was conducted in a call center. Ventilation rates were manipulated in the building's four air handling units (AHUs). Concentrations of VOCs in the AHU returns were measured on 7 days during a 13-week period. Indoor minus outdoor concentrations and emission factors were calculated. The emission factor data was subjected to principal component analysis to identify groups of co-varying compounds based on source type. One vector represented emissions of solvents from cleaning products. Another vector identified occupant sources. Direct relationships between ventilation rate and concentrations were not observed for most of the abundant VOCs. This result emphasizes the importance of source control measures for limiting VOC concentrations in buildings.
- Research Organization:
- Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
- Sponsoring Organization:
- USDOE Assistant Secretary for Energy Efficiency and Renewable Energy. Office of Building Technology, State and Community Programs. Office of Building Research and Standards (US)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 792964
- Report Number(s):
- LBNL--49535
- Country of Publication:
- United States
- Language:
- English