Calcium carbonate scale control in once-through cooling systems

Conference · · Proceedings of the American Power Conference; (USA)
OSTI ID:7067700
;  [1];  [2];  [3];  [4]
  1. Betz Lab., Inc., The Woodlands, TX (US)
  2. Betz Industrial, Bismark, ND (US)
  3. Beltz Industrial, Trevosa, PA (US)
  4. Minnkota Power Cooperative, Inc., Grand Forks, ND (USA)

This paper reports on a laboratory-scale model surface condenser used to design a successful once-through cooling water treatment program for calcium carbonate scale inhibition at Young Station. The treatment program has maintained the station's condenser cleanliness factor at approximately 100% for the duration of the treatment. The model surface condensers simulate cycled systems as well as once-through cooling systems. They are fully automated with computer-controlled chemical feed, flow, heat flux, makeup, and blowdown and data acquisition systems.

OSTI ID:
7067700
Report Number(s):
CONF-890425--
Journal Information:
Proceedings of the American Power Conference; (USA), Journal Name: Proceedings of the American Power Conference; (USA) Vol. 51; ISSN PAPWA; ISSN 0097-2126