Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Disinfection of low quality wastewaters by ultraviolet irradiation

Journal Article · · J. - Water Pollut. Control Fed.; (United States)
OSTI ID:7061997

Pilot-scale disinfection of simulated combined sewer overflow (CSO) by ultraviolet light (UV) and by high-rate chlorination were compared. Disinfection efficiency was evaluated over a range of dosages and contact times for fecal coliforms, enterococci, P. Aeruginosa, and Salmonella spp. Fecal coliform were reduced 3.0 to 3.2 logs at a UV dose of approximately 350,000..mu.. W s/cm/sup 2/. High-rate chlorination, at a contact time of 2.0 minutes and total residual chlorine concentration of approximately 25 mg/L (as Cl/sub 2/), reduced fecal coliforms by 4.0 logs. Pathogens were reduced to detection limits by both processes. Neither photoreactivation nor regrowth occurred int he disinfected effluents. The estimated capital costs of CSO disinfection by UV irradiation were consistently higher than for chlorination/dechlorination; operation and maintenance costs were similar. 19 references.

OSTI ID:
7061997
Journal Information:
J. - Water Pollut. Control Fed.; (United States), Journal Name: J. - Water Pollut. Control Fed.; (United States) Vol. 58:3; ISSN JWPFA
Country of Publication:
United States
Language:
English