Effects of voltage surges on solid-dielectric cable life
Technical Report
·
OSTI ID:6463143
- Georgia Power Co., Forest Park, GA (USA). Research Center
Lightning and fault locating voltage impulses have long been thought to cause extruded underground distribution cables to fail prematurely in service. Unfortunately, the extent of this effect has never been adequately determined. The research conducted under this contract was aimed at finding the influence of simulated lightning impulses and fault locating impulses on various types of extruded underground distribution power cables aged in the laboratory. Fifteen kV cables with two insulation thickness were investigated. Insulation materials included crosslinked polyethylene (XLPE), tree resistant crosslinked polyethylene (TRXLPE), tree resistant high molecular weight polyethylene (TRHMWPE) and ethylene propylene rubber (EPR). The cables were aged up to 640 days in the laboratory using a slightly modified version of the standard AEIC accelerated water treeing test procedure. While they aged, selected cables were exposed to 40 kV, 70 kV and 120 kV rapid rise, simulated lightning impulses. Other cable samples were exposed to a fault locating impulse, and control samples were aged without the application of an impulse. The surge effect was assessed using two methods. First, the ac breakdown and impulse breakdown strength of control and impulsed samples was compared. Second, the number of impulsed cables which failed during the aging test were compared to the number of control failures. 13 refs., 76 figs.
- Research Organization:
- Electric Power Research Inst., Palo Alto, CA (USA); Georgia Power Co., Forest Park, GA (USA). Research Center
- Sponsoring Organization:
- EPRI
- OSTI ID:
- 6463143
- Report Number(s):
- EPRI-EL-6902
- Country of Publication:
- United States
- Language:
- English
Similar Records
Effects of voltage surges on extruded dielectric cable life project update
Characterization of unaged extruded distribution cables
Effect of D. C. testing water tree deteriorated cable and a preliminary evaluation of V. L. F. as alternate
Journal Article
·
Thu Mar 31 23:00:00 EST 1994
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6985737
Characterization of unaged extruded distribution cables
Conference
·
Mon Dec 30 23:00:00 EST 1996
·
OSTI ID:524600
Effect of D. C. testing water tree deteriorated cable and a preliminary evaluation of V. L. F. as alternate
Journal Article
·
Wed Jul 01 00:00:00 EDT 1992
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:7050401
Related Subjects
24 POWER TRANSMISSION AND DISTRIBUTION
240300* -- Power Transmission Lines & Cables-- (1990-)
AGING
CABLES
CONDUCTOR DEVICES
DIELECTRIC MATERIALS
ELECTRIC CABLES
ELECTRIC DISCHARGES
ELECTRICAL EQUIPMENT
ELECTRICAL FAULTS
EQUIPMENT
FAILURE MODE ANALYSIS
FAILURES
LIGHTNING
MATERIALS
POWER DISTRIBUTION SYSTEMS
POWER TRANSMISSION
SERVICE LIFE
SURGES
SYSTEM FAILURE ANALYSIS
SYSTEMS ANALYSIS
UNDERGROUND POWER TRANSMISSION
240300* -- Power Transmission Lines & Cables-- (1990-)
AGING
CABLES
CONDUCTOR DEVICES
DIELECTRIC MATERIALS
ELECTRIC CABLES
ELECTRIC DISCHARGES
ELECTRICAL EQUIPMENT
ELECTRICAL FAULTS
EQUIPMENT
FAILURE MODE ANALYSIS
FAILURES
LIGHTNING
MATERIALS
POWER DISTRIBUTION SYSTEMS
POWER TRANSMISSION
SERVICE LIFE
SURGES
SYSTEM FAILURE ANALYSIS
SYSTEMS ANALYSIS
UNDERGROUND POWER TRANSMISSION