The adipic acid enhanced flue gas desulfurization process for industrial boilers. Volume 2. Technical assessment. Final report Feb 81-Feb 82

Technical Report ·
OSTI ID:6442699
The report gives results of an evaluation of an adipic acid enhanced limestone flue gas desulfurization (FGD) system on industrial boilers at Rickenbacker Air National Guard Base. The SO/sub 2/ removal efficiency with the adipic acid averaged 94.3% over a 30-day period. This represents a significant improvement in the performance of the system using only limestone. Economic calculations for an industrial boiler adipic acid enhanced limestone FGD system indicate a slight reduction in both capital and operating expenses relative to a limestone-only system designed for 90% SO2 control of 3.5% sulfur coal. The costs are competitive with those of the dual alkali system. The successful demonstration of the adipic acid enhanced limestone system increases the number of demonstrated technologies available to a potential user.
Research Organization:
Radian Corp., Austin, TX (USA)
OSTI ID:
6442699
Report Number(s):
PB-83-144782
Country of Publication:
United States
Language:
English