Air exchange rate measurements in an IAQ test house

Technical Report ·
OSTI ID:642845
In the past 6 years, over 1,000 tracer gas measurements have been made to determine the air exchange rates in the EPA Indoor Air Quality Test House. The major factors that affected the air exchange rate include: weather conditions, operation of the heating and air-conditioning (HAC) system, and closing or opening the interior doors. An empirical model that correlates air infiltration rate to indoor/outdoor temperature difference and outdoor wind speed can predict the air exchange rate with an average predictive error of 10%. The model also makes it possible to construct a continuous air exchange profile, with which the diurnal and annual patterns can be examined. With the HAC system on, the air exchange rate showed diurnal and annual patterns can be examined. With the HAC system on, the air exchange rate showed a moderate increase as compared to that with the system off. In a striking contrast, the interior doors had much greater impact on air exchange: under similar weather conditions, closing all interior doors doubled the air exchange rate when the HAC system was on. Type III mixing difficulty was observed in the test house. Results from extensive computer simulations showed that, for tracer decay method, air exchange rate calculated by using the data in the first hour and after 4 or 5 hours contained much greater error than that calculated by using the data in between. Recommendations are made for minimizing such error.
Research Organization:
Acurex Environmental Corp., Research Triangle Park, NC (United States); Environmental Protection Agency, Air Pollution Prevention and Control Div., Research Triangle Park, NC (United States)
Sponsoring Organization:
Environmental Protection Agency, Washington, DC (United States)
OSTI ID:
642845
Report Number(s):
PB--98-151749/XAB; CNN: Contract EPA-68-D4-0005
Country of Publication:
United States
Language:
English

Similar Records

Air infiltration rates in pre- and post-weatherized houses
Journal Article · Wed May 01 00:00:00 EDT 1985 · J. Air Pollut. Control Assoc.; (United States) · OSTI ID:5082122

Effects of building features on indoor air and pollutant movements
Technical Report · Tue Dec 31 23:00:00 EST 1991 · OSTI ID:5389401

Impact of heating and air conditioning system operation and leakage on ventilation and intercompartment transport: Studies in unoccupied and occupied Tennessee Valley homes
Journal Article · Wed Jan 31 23:00:00 EST 1990 · Journal of the Air and Waste Management Association; (USA) · OSTI ID:7157553