Measurement of harmonic currents and evaluation of the dc filter performance of the New England - Hydro-Quebec Phase I HVDC Project
Measurements of harmonic currents in the New England-Hydro-Quebec Phase I HVDC Project de transmission line are presented in this paper. Measurements were conducted to determine the cause of increased telephone interference and to evaluate the dc filter performance. The measurements revealed unexpected high levels of 3-pulse harmonic currents in the dc pole conductors. The cause is attributed to imbalances within the 6-pulse bridges caused by the converter transformer and valve stray capacitances to ground. The conventional model of the converter power circuit used as the basis for the dc filter design does not reproduce the measured 3-pulse harmonics. Modification to this model is required to account for the effect of the converter transformer and valve stray capacitances to ground.
- Research Organization:
- Ebasco Services Inc., New York, NY (US); New England Power Service Co., Westborough, MA (US)
- OSTI ID:
- 6183432
- Journal Information:
- IEEE Trans. Power Del.; (United States), Vol. 4:1
- Country of Publication:
- United States
- Language:
- English
Similar Records
A three-pulse model of d. c. side harmonic flow in HVDC systems
Active dc filter for HVDC system--A test installation in the Konti-Skan DC link at Lindome converter station
Related Subjects
13 HYDRO ENERGY
ELECTRIC CURRENTS
HARMONICS
ELECTRIC FILTERS
PERFORMANCE TESTING
HVDC SYSTEMS
QUEBEC
HYDROELECTRIC POWER PLANTS
DESIGN
POWER TRANSMISSION LINES
CANADA
CURRENTS
DC SYSTEMS
ENERGY SYSTEMS
FILTERS
NORTH AMERICA
OSCILLATIONS
POWER PLANTS
POWER SYSTEMS
TESTING
200101* - Fossil-Fueled Power Plants- Cooling & Heat Transfer Equipment & Systems
130300 - Hydro Energy- Plant Design & Operation