Title: Measurement of harmonic currents and evaluation of the dc filter performance of the New England - Hydro-Quebec Phase I HVDC Project

Journal Article · · IEEE Trans. Power Del.; (United States)
DOI:https://doi.org/10.1109/61.19270· OSTI ID:6183432

Measurements of harmonic currents in the New England-Hydro-Quebec Phase I HVDC Project de transmission line are presented in this paper. Measurements were conducted to determine the cause of increased telephone interference and to evaluate the dc filter performance. The measurements revealed unexpected high levels of 3-pulse harmonic currents in the dc pole conductors. The cause is attributed to imbalances within the 6-pulse bridges caused by the converter transformer and valve stray capacitances to ground. The conventional model of the converter power circuit used as the basis for the dc filter design does not reproduce the measured 3-pulse harmonics. Modification to this model is required to account for the effect of the converter transformer and valve stray capacitances to ground.