The purpose of this study is to determine the Reliability, Availability and Maintainability (RAM) at the 30% design phase of a Jet Fuel Storage Tank Facility that is to be installed at the Tinker Air Force Base, Tulsa, Oklahoma. The Jet Fuel Storage Tank Facility was divided into four subsystems: Fuel Storage and Pipeline Transfer Pumps; Truck Unloading and Loading; Fire Protection (foam and water supply systems); and Electric Power. The RAM analysis was performed on four functions of these subsystems: transferring fuel from the two new 55K barrel storage tanks to the existing fuel pipeline system; transferring fuel from the two 55K barrel storage tanks to the aircraft refueler trucks; transferring fuel from the road transport trucks to the aircraft refueler trucks; and fire protection. A fault tree analysis was performed on each functional system. The quantification was performed for several mission times.

Research Organization:
EG and G Idaho, Inc., Idaho Falls (USA)
DOE Contract Number:
AC07-76ID01570
OSTI ID:
6068421
Report Number(s):
EGG-REQ-7807; ON: DE88001579
Resource Relation:
Other Information: Portions of this document are illegible in microfiche products
Country of Publication:
United States