Biofouling detection monitoring devices: status assessment. Final report
Technical Report
·
OSTI ID:5875191
An inventory of devices to detect and monitor biofouling in power plant condenser systems was prepared. The inventory was developed through a review of manufacturers' product information brochures, a general literature review, and limited personal contact with users and manufacturers. Two macrofouling and seventeen microfouling detection devices were reviewed. A summary analysis of the principal features of each device was prepared. Macrofouling devices are generally simple devices located at or near cooling water intakes. They monitor the growth of larger organisms such as mussels, barnacles, and large seaweeds. Microfouling detectors are usually located in or near the condenser tubes. They detect and monitor the growth of slime films on the tubes. Some of the devices measure changes in heat transfer or pressure drop in the condenser tubes. Other types include condenser simulators, biofilm samplers, or devices that measure the acoustic properties of the fouling films. Most devices are still in the development stage. Of the few available for general use, the type that measures heat transfer and/or pressure drop are developed to a greater degree than the other types. Recommendations for further research into development of a biofouling detection and monitoring devices include a side-by-side field comparison of selected devices, and the continued development of an effective acoustic device.
- Research Organization:
- Battelle New England Marine Research Lab., Duxbury, MA (USA); Battelle Columbus Labs., OH (USA); Pacific Northwest Labs., Richland, WA (USA)
- DOE Contract Number:
- AC06-76RL01830
- OSTI ID:
- 5875191
- Report Number(s):
- EPRI-CS-3914; ON: DE85009024
- Country of Publication:
- United States
- Language:
- English
Similar Records
Keeping biofouling at bay
Macrofouling control technology update
Biofouling monitoring and control program at the Boston Edison Pilgrim Nuclear Station: A twelve year history
Journal Article
·
· EPRI J.; (United States)
·
OSTI ID:6064121
Macrofouling control technology update
Conference
·
Mon Dec 30 23:00:00 EST 1996
·
OSTI ID:549946
Biofouling monitoring and control program at the Boston Edison Pilgrim Nuclear Station: A twelve year history
Technical Report
·
Thu Aug 01 00:00:00 EDT 1996
·
OSTI ID:414824
Related Subjects
20 FOSSIL-FUELED POWER PLANTS
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
440300 -- Miscellaneous Instruments-- (-1989)
47 OTHER INSTRUMENTATION
ACOUSTIC TESTING
BIOLOGICAL FOULING
CONDENSERS
COST
DESIGN
EVALUATION
FOULING
MATERIALS TESTING
MONITORING
NONDESTRUCTIVE TESTING
TESTING
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
440300 -- Miscellaneous Instruments-- (-1989)
47 OTHER INSTRUMENTATION
ACOUSTIC TESTING
BIOLOGICAL FOULING
CONDENSERS
COST
DESIGN
EVALUATION
FOULING
MATERIALS TESTING
MONITORING
NONDESTRUCTIVE TESTING
TESTING