Circuit description of the power systems for pulsed septum magnets at APS
This paper describes the design and simulation of power circuits for the 4 Advanced Photon Source (APS) pulsed septum magnets which will be transformer type or transformer coupled to their switching circuits. Three are for synchrotron injection, extraction and Storage Ring injection, operating at a 2 Hz pulse rate; one is for the Positron Accumulator Ring (PAR) operating at a 60 Hz pulse rate for both injection and extraction. The septum current pulse is approximately a half-sine-wave with a base width of approximately 1/3 ms and a peak current, repeatable within {plus minus} 0.05%, in the transformer primary between 3.5 kA and 4.7 kA. The septum magnets have a primary inductance between 16 {mu}H and 23 {mu}H. Circuit design considerations of the switching, logic and simulations are presented. 2 refs., 5 figs.
- Research Organization:
- Argonne National Lab., IL (USA)
- Sponsoring Organization:
- DOE; USDOE, Washington, DC (USA)
- DOE Contract Number:
- W-31109-ENG-38
- OSTI ID:
- 5769906
- Report Number(s):
- ANL/CP-73045; CONF-910505--43; ON: DE91011995
- Country of Publication:
- United States
- Language:
- English
Similar Records
A pulsed septum magnet for the APS
Pulsed power supply for PAR injection/extraction septum magnet
Related Subjects
430303* -- Particle Accelerators-- Experimental Facilities & Equipment
CAPACITORS
COMPUTERIZED SIMULATION
ELECTRICAL EQUIPMENT
ELECTROMAGNETS
ELECTRONIC CIRCUITS
ELECTRONIC EQUIPMENT
EQUIPMENT
LOGIC CIRCUITS
MAGNETS
POWER SUPPLIES
RADIATION SOURCES
SEPTUM MAGNETS
SIMULATION
SWITCHING CIRCUITS
SYNCHROTRON RADIATION SOURCES