High temperature hot water distribution system study
Technical Report
·
OSTI ID:564553
The existing High Temperature Hot Water (HTHW) Distribution System has been plagued with design and construction deficiencies since startup of the HTHW system, in October 1988. In October 1989, after one year of service, these deficiencies were outlined in a technical evaluation. The deficiencies included flooded manholes, sump pumps not hooked up, leaking valves, contaminated HTHW water, and no cathodic protection system. This feasibility study of the High Temperature Hot Water (HTHW) Distribution System was performed under Contract No. DACA0l-94-D-0033, Delivery Order 0013, Modification 1, issued to EMC Engineers, Inc. (EMC), by the Norfolk District Corps of Engineers, on 25 April 1996. The purpose of this study was to determine the existing conditions of the High Temperature Hot Water Distribution System, manholes, and areas of containment system degradation. The study focused on two areas of concern, as follows: * Determine existing conditions and areas of containment system degradation (leaks) in the underground carrier pipes and protective conduit. * Document the condition of underground steel and concrete manholes. To document the leaks, a site survey was performed, using state-of-the-art infrared leak detection equipment and tracer gas leak detection equipment. To document the condition of the manholes, color photographs were taken of the insides of 125 manholes, and notes were made on the condition of these manholes.
- Research Organization:
- EMC Engineers, Inc., Roswell, GA (United States)
- OSTI ID:
- 564553
- Report Number(s):
- AD-A--330813/7/XAB; EMC--1406-013; CNN: Contract DACA01-94-D-0033
- Country of Publication:
- United States
- Language:
- English
Similar Records
High temperature hot water distribution system study, Directorate of Public Works, Fort Drum, New York; executive summary. Final report
History of waste tank 24, 1962--1974
System provides secondary containment for aboveground storage tanks
Technical Report
·
Sat Nov 30 23:00:00 EST 1996
·
OSTI ID:564505
History of waste tank 24, 1962--1974
Technical Report
·
Sat Mar 31 23:00:00 EST 1979
·
OSTI ID:6308666
System provides secondary containment for aboveground storage tanks
Journal Article
·
Sun Oct 28 23:00:00 EST 1990
· Oil and Gas Journal; (USA)
·
OSTI ID:5913708