Ventilation measurements in large office buildings
Conference
·
· ASHRAE Trans.; (United States)
OSTI ID:5551535
Ventilation rates were measured in nine office buildings using an automated tracer gas measuring system. The buildings range in size from a two-story federal building with a floor area of about 20,000 ft/sup 2/ (1900 m/sup 2/) to a 26-story office building with a floor area of 700,000 ft/sup 2/ (65,000 m/sup 2/). The ventilation rates were measured for about 100 hours in each building over a range of weather conditions. The results are presented and examined for variation with time and weather. In most cases, the ventilation rate of a building is similar for hot and cold weather. In mild weather, outdoor air is used to cool the building and the ventilation rate increases. In the buildings where infiltration is a significant portion of the total ventilation rate, this total rate exhibits a dependence on weather conditions. The measured ventilation rates are discussed in relation to the outdoor air intake strategy in each building. The ventilation rates are also compared to the design rates in the buildings and ventilation rates based on the ASHRAE Standard 62-81. Some of the buildings are at times operated at lower ventilation rates than recommended in Standard 62-81.
- Research Organization:
- Center for Building Technology, National Bureau of Standards, Gaithersburg, MD
- OSTI ID:
- 5551535
- Report Number(s):
- CONF-850606-
- Conference Information:
- Journal Name: ASHRAE Trans.; (United States) Journal Volume: 91:2A
- Country of Publication:
- United States
- Language:
- English
Similar Records
A study of ventilation and carbon dioxide in an office building
The impact of ventilation rates on the design of office buildings
Ventilation, carbon dioxide and ASHRAE standard 62-1989
Conference
·
Fri Dec 30 23:00:00 EST 1994
·
OSTI ID:33326
The impact of ventilation rates on the design of office buildings
Conference
·
Thu Dec 31 23:00:00 EST 1981
· ASHRAE Trans.; (United States)
·
OSTI ID:6143563
Ventilation, carbon dioxide and ASHRAE standard 62-1989
Journal Article
·
Thu Jul 01 00:00:00 EDT 1993
· ASHRAE Journal (American Society of Heating, Refrigerating and Air-Conditioning Engineers); (United States)
·
OSTI ID:5791824
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320102* -- Energy Conservation
Consumption
& Utilization-- Office Buildings-- (-1987)
AIR FLOW
AIR INFILTRATION
BUILDINGS
COMPARATIVE EVALUATIONS
DATA
DESIGN
EXPERIMENTAL DATA
FLOORS
FLOW RATE
FLUID FLOW
GAS FLOW
INFORMATION
MONITORING
NUMERICAL DATA
OFFICE BUILDINGS
OPERATION
PERFORMANCE TESTING
STANDARDS
SURFACE AREA
SURFACE PROPERTIES
TESTING
TIME DEPENDENCE
VENTILATION
VENTILATION SYSTEMS
WEATHER
320102* -- Energy Conservation
Consumption
& Utilization-- Office Buildings-- (-1987)
AIR FLOW
AIR INFILTRATION
BUILDINGS
COMPARATIVE EVALUATIONS
DATA
DESIGN
EXPERIMENTAL DATA
FLOORS
FLOW RATE
FLUID FLOW
GAS FLOW
INFORMATION
MONITORING
NUMERICAL DATA
OFFICE BUILDINGS
OPERATION
PERFORMANCE TESTING
STANDARDS
SURFACE AREA
SURFACE PROPERTIES
TESTING
TIME DEPENDENCE
VENTILATION
VENTILATION SYSTEMS
WEATHER