A study of ventilation and carbon dioxide in an office building

Conference ·
OSTI ID:33326
; ;  [1]
  1. National Inst. of Standards and Technology, Gaithersburg, MD (United States). Building and Fire Research Lab.
Ventilation rates and indoor carbon dioxide levels were monitored for two years in a new office building near St. Louis, Missouri. These measurements were made to assess the operation and performance of the ventilation system in this building and to investigate the relationship between indoor carbon dioxide levels and air change rates. Ventilation rates were measured with the tracer gas decay technique using an automated measuring system. Indoor carbon dioxide concentrations were also measured with an automated system. The ventilation rates exhibited a dependence on outdoor temperature that was expected based on the heating, ventilating, and air-conditioning (HVAC) system`s controls. The air change rates under conditions of minimum outdoor air intake were about 0.5 air changes per hour (ach), which is lower than both the air change rate corresponding to the building design value for minimum outdoor air intake and the rate that corresponds to the recommended minimum outdoor airflow per person in ASHRAE Standard 62-1989. The indoor carbon dioxide concentrations were generally lower than the 1,000-ppm guideline in Standard 62. The relationship between the indoor carbon dioxide levels and the building air change rates was similar to that seen in other office buildings. These results are presented as part of a discussion on the use of equilibrium analysis of carbon dioxide concentrations to determine building air change rates. This discussion points out limitations in the use of equilibrium analysis of carbon dioxide concentrations in office buildings.
OSTI ID:
33326
Report Number(s):
CONF-9406105--
Country of Publication:
United States
Language:
English

Similar Records

Environmental evaluation of the Federal Records Center in Overland, Missouri
Technical Report · Sat Aug 01 00:00:00 EDT 1992 · OSTI ID:7008710

Ventilation, carbon dioxide and ASHRAE standard 62-1989
Journal Article · Thu Jul 01 00:00:00 EDT 1993 · ASHRAE Journal (American Society of Heating, Refrigerating and Air-Conditioning Engineers); (United States) · OSTI ID:5791824

A study of ventilation measurement in an office building
Journal Article · Fri Sep 01 00:00:00 EDT 1995 · American Society for Testing and Materials, Special Technical Publication · OSTI ID:169999