Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

A study of ventilation measurement in an office building

Journal Article · · American Society for Testing and Materials, Special Technical Publication
DOI:https://doi.org/10.1520/STP14687S· OSTI ID:169999
;  [1]
  1. National Inst. of Standards and Technology, Gaithersburg, MD (United States). Building and Fire Research Lab.
The National Institute of Standards and Technology has conducted a study of ventilation and ventilation measurement techniques in the Bonneville Power Administration (BPA) Building in Portland, Oregon. The project involved the use of the following outdoor air ventilation measurement techniques: tracer gas decay measurements of whole-building air change rates, the determination of air change rates based on peak carbon dioxide (CO{sub 2}) concentrations, the determination of percent outdoor air intake using tracer gas (sulfur hexafluoride and occupant-generated CO{sub 2}), and direct airflow rate measurements within the air handling system. In addition, air change rate measurements made approximately three years apart with an automated tracer gas decay system were compared. Airflow rates were measured in the air handling system ductwork using pitot tube, hot-wire anemometer, and vane anemometer traverses, and good agreement was obtained between the different techniques. While accurate determinations of percent outdoor air intake were achieved using tracer gas techniques, the use of CO{sub 2} detector tubes yielded unreliable results. Reliable determinations of ventilation rates per person were made based on SF{sub 6} decay and direct airflow rate measurements, but the use of peak CO{sub 2} concentrations led to overestimations of building air change rates. The measured values of the whole-building air change rates, and their dependence on outdoor air temperature, did not change significantly over a three-year period. The whole-building air change rate under minimum outdoor air intake conditions was determined to be twice the outdoor air intake rate provided by the minimum outdoor air intake fans due to leakage through the main outdoor air intake dampers.
Sponsoring Organization:
USDOE
OSTI ID:
169999
Report Number(s):
CONF-931017--
Journal Information:
American Society for Testing and Materials, Special Technical Publication, Journal Name: American Society for Testing and Materials, Special Technical Publication Journal Issue: 1255; ISSN 0066-0558; ISSN ASTTA8
Country of Publication:
United States
Language:
English

Similar Records

Simultaneous measurements of infiltration and intake in an office building
Conference · Mon Jun 01 00:00:00 EDT 1987 · ASHRAE Trans.; (United States) · OSTI ID:6424739

A study of ventilation and carbon dioxide in an office building
Conference · Fri Dec 30 23:00:00 EST 1994 · OSTI ID:33326

Air change rates and carbon dioxide concentrations in a high-rise office building
Conference · Fri Dec 30 23:00:00 EST 1994 · OSTI ID:33325