Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

BOD limit in synfuel plants' cooling-tower makeup

Conference ·
OSTI ID:5434254
A model cooling tower/trickling filter was used to study acceptable BOD level in wastewater reuse as cooling system makeup and the effect on the system biofouling. Tap water was used to makeup for evaporation and blowdown while phenol solution was metered as the contaminant, into the circulating water. The phenol was degraded in the tower with less than 2 ppM in circulation at equivalent makeup concentrations below 1200 mg BOD/L. The rate of biofouling, measured by heat transfer coefficient, was correlated with phenol loading rates. Makeup concentrations below 1000 mg BOD/L gave low fouling rates while concentration above 1200 mg BOD/L resulted in intolerable fouling of exchanger tubes.
Research Organization:
Water Purification Associates, Cambridge, MA (USA)
DOE Contract Number:
AC02-80EV10367
OSTI ID:
5434254
Report Number(s):
DOE/EV/10367-24; CONF-820532-1; ON: DE82012321
Country of Publication:
United States
Language:
English