Tube vibration in industrial size test heat exchanger
Tube vibration data from tests of a specially built and instrumented, industrial-type, shell-and-tube heat exchanger are reported. The heat exchanger is nominally 0.6 m (2 ft) in dia and 3.7 m (12 ft) long. Both full tube and no-tubes-in-window bundles were tested for inlet/outlet nozzles of different sizes and with the tubes supported by seven, equally-spaced, single-segmental baffles. Prior to water flow testing, natural frequencies and damping of representative tubes were measured in air and water. Flow testing was accomplished by increasing the flow rates in stepwise fashion and also by sweeping through a selected range of flow rates. The primary variables measured and reported are tube accelerations and/or displacements and pressure drop through the bundle. Tests of the full tube bundle configuration revealed tube rattling to occur at intermediate flow rates, and fluidelastic instability, with resultant tube impacting, to occur when the flow rate exceeded a threshold level; principally, the four-span tubes were involved in the regions immediately adjacent to the baffle cut. For the range of flow rates tested, fluidelastic instability was not achieved in the no-tubes-in-window bundle; in this configuration the tubes are supported by all seven baffles and are, therefore, stiffer.
- Research Organization:
- Argonne National Laboratory (ANL), Argonne, IL (United States)
- DOE Contract Number:
- W-31109-ENG-38
- OSTI ID:
- 5377380
- Report Number(s):
- ANL-CT-80-18
- Country of Publication:
- United States
- Language:
- English
Similar Records
Tube vibration in industrial size test heat exchanger (30/sup 0/ triangular layout - six crosspass configuration)
Flow-induced tube vibration thresholds in heat exchangers from shellside water tests
Tube vibration in industrial size test heat exchanger (22 additional configurations)
Technical Report
·
Thu Oct 01 00:00:00 EDT 1981
·
OSTI ID:5593138
Flow-induced tube vibration thresholds in heat exchangers from shellside water tests
Conference
·
Sat Dec 31 23:00:00 EST 1983
·
OSTI ID:6317505
Tube vibration in industrial size test heat exchanger (22 additional configurations)
Technical Report
·
Sat Nov 30 23:00:00 EST 1985
·
OSTI ID:6215505