Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Dynamic performance of a prototype solar-assisted heat pump

Technical Report ·
DOI:https://doi.org/10.2172/5285312· OSTI ID:5285312
A prototype water-air solar assisted heat pump (SAHP), has been tested as part of a contract for the development of marketable solar assisted heat pumps. The steady state test results indicate that the nominal performance goal for the prototype, COP of 6 to 90/sup 0/F entering water temperature, was achieved. The transient and cycling tests of the Northrup prototype are described. Tests were performed while the unit cycled under a conventional and modified control mode. Results indicate that cycling performance can be significantly enhanced by operation under the modified control mode where the supply fan is run after the compressor is turned off to extract heat still available at the end of the duty cycle.
Research Organization:
Brookhaven National Lab., Upton, NY (USA)
DOE Contract Number:
AC02-76CH00016
OSTI ID:
5285312
Report Number(s):
BNL-51503; ON: DE82012330
Country of Publication:
United States
Language:
English