High voltage VLF testing of power cables

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.584323· OSTI ID:492174
; ;  [1];  [2];  [3]
  1. Cable Technology Labs., Inc., New Brunswick, NJ (United States)
  2. Ontario Hydro, Toronto, Ontario (Canada)
  3. EPRI, Washington, DC (United States)

This publication describes a laboratory test program conducted with the objective to develop a test that would replace the existing dc withstand test. The article describes the methodology used to establish the voltage duration and magnitude of VLF (0.1 Hz) high voltage field tests suitable for crosslinked polyethylene (XLPE) insulated power cable. The results show that the voltage breakdown of laboratory aged XLPE cable at 0.1 Hz is approximately equal to that at 60 Hz, that proof tests at 0.1 Hz is approximately equal to that at 60 Hz, that proof tests at 0.1 Hz cause very little damage to the cable, and that 0.1 Hz testing appears to be a satisfactory alternate to dc testing. Preliminary values are suggested for voltage magnitude and time duration of cable acceptance, maintenance and proof tests at 0.1 Hz for XLPE cable rated up to 35 kV. A program is underway to similarly evaluate samples of service-aged XLPE cable; as well as to demonstrate the use of the preliminary test values at typical utility installations.

Sponsoring Organization:
Electric Power Research Inst., Palo Alto, CA (United States)
OSTI ID:
492174
Report Number(s):
CONF-9609171--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 2 Vol. 12; ISSN ITPDE5; ISSN 0885-8977
Country of Publication:
United States
Language:
English

Similar Records

Effect of D. C. testing water tree deteriorated cable and a preliminary evaluation of V. L. F. as alternate
Journal Article · Wed Jul 01 00:00:00 EDT 1992 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7050401

Effect of dc testing on extruded cross-linked polyethylene insulated cables
Technical Report · Thu Dec 31 23:00:00 EST 1992 · OSTI ID:6688245

Effect of dc testing on extruded cross-linked polyethylene insulated cables
Technical Report · Thu Dec 31 23:00:00 EST 1992 · OSTI ID:10138387