Robust continuous speed governor control for small-signal and transient stability

Journal Article · · IEEE Transactions on Power Systems
DOI:https://doi.org/10.1109/59.574932· OSTI ID:484895
;  [1];  [2]
  1. Electricite de France, Clamart (France)
  2. Supelec, Gif-sur-Yvette (France)

A robust continuous governor control for small-signal and transient stability is proposed. The turbine under consideration is a steam turbine with two sections and is of reheat type. The controller can b viewed as including the speed droop governor and the fast-valving; the latter is not standard, in that it generates a continuous control. Hence, the disadvantages of the (usual) bang-bang fast-valving are avoided. The control signal is generated by two controllers, with the first one for small disturbances and the second one for large disturbances. The authors` approach is innovative in that both controllers have the same structure and only differ in the tuning of their parameters. They generate a continuous control and are switched with a bumpless transition to ensure the continuity of the overall control. The most important non-linearity of the turbine is taken into account, and a feedback linearization is made--but in a somewhat unusual manner to obtain a robust controller. A linear quadratic control is also used to ensure that the steady-state objectives are met and that good transients are obtained. Simulations with the EUROSTAG software show improved efficiency with the proposed controller compared with the current one, especially in the case of a short-circuit, and islanding or a temporary loss of synchronism of the machine considered; the current controller has a standard structure, including a bang-bang fast-valving.

OSTI ID:
484895
Report Number(s):
CONF-960111--
Journal Information:
IEEE Transactions on Power Systems, Journal Name: IEEE Transactions on Power Systems Journal Issue: 1 Vol. 12; ISSN ITPSEG; ISSN 0885-8950
Country of Publication:
United States
Language:
English

Similar Records

Design of an optimal robust governor for hydraulic turbine generating units
Journal Article · Tue Feb 28 23:00:00 EST 1995 · IEEE Transactions on Energy Conversion · OSTI ID:40296

Mitigation of Remedial Action Schemes by Decentralized Robust Governor Control
Conference · Tue Apr 15 00:00:00 EDT 2014 · OSTI ID:1178873

The role of governor control in transient stability of super-conducting turbo-generators
Journal Article · Sat Feb 28 23:00:00 EST 1987 · IEEE Trans. Power Electronics; (United States) · OSTI ID:6612726