Transient stability control of an area network
Conference
·
OSTI ID:438690
- Academia Sinica, Beijing (China). Inst. of Systems Science
- Tsinghua Univ., Beijing (China). Dept. of Electrical Engineering
- Power System Central Dispatching Bureau of Jilin Province, Changchun (China)
Design of a generator tripping system to enhance the transient stability of an area power network using a quasi-real-time method is presented. The Hunjiang power system in China is selected to implement the design scheme. The necessary hardware and software that are required to implement the control scheme, is outlined. The fast transient stability assessment, which uses the technology such as dynamic equivalence, state estimation and direct transient energy function method, is provided to form a control strategy table. According to this table, when a large disturbance occurs, the estimated amount of generation will be tripped to maintain the rest of generators stable in power system. The studies reveal that the generator tripping system can adapt to the changes of load and generation in the system as well as changes in the network topology. This paper also outlines the new features compared with the existing conventional control system and proposes the strategies in the event of failure of the generator tripping system.
- OSTI ID:
- 438690
- Report Number(s):
- CONF-951136--; ISBN 0-7803-2981-3
- Country of Publication:
- United States
- Language:
- English
Similar Records
Feedback Control Strategy for Transient Stability Application
Transient stability assessment for network topology changes: Application of energy margin analytical sensitivity
Journal Article
·
Fri Aug 19 00:00:00 EDT 2022
· Energies
·
OSTI ID:1887387
Transient stability assessment for network topology changes: Application of energy margin analytical sensitivity
Journal Article
·
Mon Aug 01 00:00:00 EDT 1994
· IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6911532