KEPCO 765 kV transmission system development corona and electric field effects studies
Conference
·
OSTI ID:433830
- Korea Electric Power Research Inst., Daejeon (Korea, Republic of)
- Korea Electrotechnology Research Inst., Kyungnam (Korea, Republic of)
- Han Yang Univ., Kyunggi (Korea, Republic of)
This paper describes corona and electric field effects studies of a 765 kV double circuit test line. In Korea there are many mountains and it is very difficult to get the right of way because the population density is very high and the territory is small. So Korea Electric Power Corporation (KEPCO) decided to build one double-circuit 765 kV line of vertical arrangement configuration instead of two single-circuit 765 kV lines of horizontal configuration. Corona performance on several candidate conductor bundles has been investigated with a corona cage since 1984 by KEPRI. A bundle of 6-Rail(29.61 mm) conductors per phase is the optimum and its AN level L{sub 60} in the corona cage was measured as 45.0 dB(A) in GE method. To investigate electrical environmental impact of the future commercial line with this conductor bundle, KEPRI built a full scale 765 kV test line in 1993 as the second step study. Long-term measurements have been made in this double-circuit test line. The authors have found that the Audible Noise (AN) data were very close to the predicted by BPA Corona and Field Effects computer program, however, the RI data in fair weather was higher than the predicted by the BPA program by 2.4 dB({mu}V/m). Audible Noise Level L{sub 50} in foul weather is below 50 dB(A). The authors think the 6-Rail conductors bundle is the optimum size in 765kV double-circuit transmission line from the environmental view-point.
- OSTI ID:
- 433830
- Report Number(s):
- CONF-951136--; ISBN 0-7803-2981-3
- Country of Publication:
- United States
- Language:
- English
Similar Records
Research on uhv transmission nears completion of single-phase testing at 1000 to 1500 kV
Investigation of the corona performance of conductor bundles for 800-kV transmission
Bipolar HVDC transmission-system study between +- 600 kV and +- 1200 kV: corona studies, Phase II
Journal Article
·
Sun Dec 31 23:00:00 EST 1972
· EEI (Edison Elec. Inst.) Bull., v. 41, no. 4, pp. 190-192
·
OSTI ID:4330563
Investigation of the corona performance of conductor bundles for 800-kV transmission
Conference
·
Tue Dec 31 23:00:00 EST 1974
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:7295343
Bipolar HVDC transmission-system study between +- 600 kV and +- 1200 kV: corona studies, Phase II
Technical Report
·
Tue Nov 30 23:00:00 EST 1982
·
OSTI ID:6593314